EP 800

Bottom Padding

This series is for positioning of pneumatic actuator oper-ated control valves. Input signal 4 to 20mA DC is changed to air pressure. Accurate positioning is achieved by having valve position feedback from valve stem.

SPECIFICATIONS

Bottom Padding

Type for Single Action for Double Action EPC800 for double acting | EPB800 for 5200LA actuator
Input signal / characteristic 4 to 20, 4 to 12, 12 to 20 mA DC / Linear
Air supply 140 to 700 KPa
Single acting type Double acting type
Linearity/Hysteresis +/-1.0% / 0.5% +/-1.5% / 0.8%
Response level/Repeatability 0.1% / 0.2% 0.2% / 0.3%
Air consumption Output air pressure(50%)
5 Nl/min. at Sup. 140 KPa [gaug]
Output air pressure(50%) 15 Nl/min. at Sup. 400 KPa [gaug]
Max. capacity Output atmosphere
175 Nl/min. at Sup. 140 KPa [gaug]
Output atmosphere 400 Nl/min. at Sup. 400 KPa [gaug]
Enclosure Weather proof type, Explosion proof type, intrinsically safe explosion proof type
Air/Electric wiring connection Rc. 1/4 / G1/2
Environment temp. Standard model: -20 to +80o, Low temp.model: -50 to +60o, High Temp.model: 0 to +100o